Troubleshooting Common UPS faults 1

Common faults: When the mains is active, a mains power failure alarm is generated for the UPS.

main content

Possible cause

1) Mains input circuit breaker trip.

2) The input AC line is in poor contact.

3) The mains input voltage is too high, too low, or the frequency is abnormal.

4) The UPS input circuit breaker or switch is damaged or the fuse is blown.

5) The UPS internal mains detection circuit is faulty.

Treatment method

1) Check the input circuit breaker.

2) Check the input line.

3) If the mains is abnormal, do not deal with it or start the generator power supply.

4) Replace the damaged circuit breaker, switch or fuse.

5) Check the UPS mains detection loop.

When the mains is normal, UPS output is normal. When the mains power is cut off, the load is also cut off.

UPS BATTERY SERIES

UPS (Uninterruptible Power Supply) batteries are an important component of power supply systems designed to provide stable power support for electronic devices.

Extended reading

UPS User Guide

UPS User Guide Uninterruptible power supplies (UPS) are an important...

THE ESSC Brand promise

Global supply

Our products sell well all over the world, covering many countries and regions, through the global logistics network, to provide customers with convenient purchasing experience.

Rigorous quality

We adhere to the highest quality control standards to ensure every product meets industry regulations and customer expectations, earning trust through consistent excellence.

Excellent service

With a customer-centric approach, we provide prompt responses, professional support, and personalized services, aiming to deliver the best user experience and long-term value.

QUICK INQUIRY

Please enable JavaScript in your browser to complete this form.
Name