Maintain the battery module after the capacity divider test

Follow-up maintenance of the battery module after the capacity division test includes the following aspects:

Battery pack connection point check

Check the connection points of the battery pack to ensure tight contact and no oxidation, and apply petroleum jelly to prevent further oxidation.

Appearance inspection

Check the appearance of the battery regularly to see if there is mechanical damage, whether there is a small animal carcass in the device, whether there is conductive dirt or dust inside the device, and whether the dust affects the heat dissipation.

Voltage measurement

Measure the voltage of the battery pack and the voltage of each battery at least once a month to ensure that the voltage of each battery is between 13.5-14V. If the battery voltage is low or uneven, handle it in time.

Simulated mains loss test

Consciously let the battery discharge to the DC bus, after the normal operation, immediately restore the AC power supply, the battery should be able to automatically cut off the discharge circuit, the operation time of the test is not more than 5 minutes, to ensure that the UPS output is uninterrupted, the simulated power loss test is carried out at least once every three months.

Check discharge test

Check the capacity of the battery once a year, understand the actual operating capacity of the battery, and activate the battery pack once, so that the battery capacity is uniform.

Mains power verification

Check the mains power supply every year. Disconnect the main power supply and standby power supply respectively from the incoming cabinet to check the integrity of the incoming switch.

Switching module test

Periodically inspect all UPS switching modules every year to check whether the switching function of the switching module is accurate and whether the inverter function is normal.

Control system check

Check the UPS control system regularly, including whether the display module is consistent with the operation condition, and no black screen or garbled characters are displayed. If this occurs, replace the display module as soon as possible; Check whether there is abnormal sound on the control screen, and deal with the alarm and other abnormal phenomena in time; Check the operation buttons on the display control panel and confirm that the functions of each button are normal.

Battery wire inspection

Check whether the cables from the battery string to the UPS are aged. If the cables are aged, replace them with those with the same current carrying area in time to avoid unnecessary cable length.

Communication and data check

normal and the data is accurate. Handle any exception in a timely manner.

Load capacity check

Ensure that the connected load capacity does not exceed two-thirds of the UPS power capacity.

Periodic discharge

The work of the energy storage battery is all in the floating charge state, to charge and discharge regularly, it is appropriate to discharge once every 3 months or so, and at least once a year. Before discharge, the battery pack should be charged in order to achieve the balance of the whole battery.

CONCLUSION

Through the above maintenance steps, you can ensure the performance and safety of the battery module after the capacitance test, extend the service life of the battery, and ensure the stable operation of the UPS system.

UPS BATTERY SERIES

UPS (Uninterruptible Power Supply) batteries are an important component of power supply systems designed to provide stable power support for electronic devices.

Extended reading

THE ESSC Brand promise

Global supply

Our products sell well all over the world, covering many countries and regions, through the global logistics network, to provide customers with convenient purchasing experience.

Rigorous quality

We adhere to the highest quality control standards to ensure every product meets industry regulations and customer expectations, earning trust through consistent excellence.

Excellent service

With a customer-centric approach, we provide prompt responses, professional support, and personalized services, aiming to deliver the best user experience and long-term value.

QUICK INQUIRY

Please enable JavaScript in your browser to complete this form.
Name